 SIGNAL CABLES
0,5-CXKE-R, 0,5-CXFE-R, 0,5-CHKE-R, 0,5-CHFE-R

Substitute: NCYKY, NCYKFY,NCEY, NCEFY

APPLICATION

Signal cables with low fire propagation according to IEC 60332-3A, halogen-free, with minimum smoke formation by burning according to IEC 61 034 and low smoke corrosivity by IEC 60 754. They have copper conductors with insulation and jacket from halogen-free materials. Cables are dedicated for nominal voltage 0,3/0,5 kV for fixed and free installation in normal and wet surroundings (STN 33 0300). Cables may be used also in surrounding with fire danger and they may be installed on flammable base.


CONSTRUCTION

1. Copper round conductor - solid or stranded.
2. Core insulation from cross-linked polyethylene or on EVA co-polymer base. Cores are stranded together.
3. Wrapping with Al-PET tape and tinned copper wires (for type CXFE and CHFE only).
4. Flame retardant filling cover.
5. Flame retardant polyethylene jacket, orange colour with description according to agreement.


Tab.1. Cable dimensions

Conductor
cross-section
[mm2]

Insulation thickness
[mm]

Jacket thickness
[mm]

Core number

1

0,6

1,2

2 - 37

1,5

0,7

1,2

2 - 37

2,5

0,7

1,2

2 - 19

 

Tab.2. Sectional series of produced cables

Core number

Conductor cross-section
[mm2]

Cable weight
[kg/km]

Informative
cable diameter
[mm]

Current
loading in air
[A]

2

1

114

10

20

2

1.5

150

10.5

30

2

2,5

200

11.5

40

3

1

165

10.5

18

3

1,5

170

11

25

3

2,5

237

13

34

4

1

170

12.5

16

4

1,5

216

13.5

24

4

2,5

302

15

32

5

1

193

12.5

14

5

1,5

252

14

22

5

2,5

342

16

30

7

1

212

13

11

7

1,5

275

14

15

7

2,5

415

16

21

9

1

293

16

10

9

1,5

390

17.5

14

9

2,5

466

19.5

19

12

1

360

15.5

9

12

1,5

410

17

13

12

2,5

600

20.5

18

19

1

460

18.5

7

19

1,5

660

21

12

19

2,5

930

24

17

24

1

552

21,5

7

24

1,5

780

23

10


PARAMETERS FOR INSTALLATION AND USING


Maximal allowed temperature in service 90 � C, by overload 120 � C, by short circuit 250 � C.
Minimal once bending radius - 6-times cable diameter.
Minimal allowed temperature for fixed installation -40 �C, for free installation -20 �C.
Minimal temperature by installation (mounting): -15 � C.